The Local Power of Energy, The Control of the Future
The Local Power of Energy, The Control of the Future
It is a Voltage Indicator used in the cubicles of MV Switching Facilities to indicate whether energy is present on the busbar. The KGS 03 allows for Phase-Phase and Phase-Ground voltage measurements via the voltage measurement terminals located on the front panel, and the voltage of each phase can be monitored individually through the LEDs on the front face. To protect against overvoltages that may occur in the system, a "surge arrester" is integrated within the KGS 03.
Designed in accordance with the IEC 61243-5 standard, the KGS 03 continuously monitors the busbar voltage and lights its LEDs when $U > 10\% U_n$. When $U < 10\% U_n$, the LEDs are turned off. It is produced for different voltages based on the capacitance values of the Capacitive Voltage Divider Insulators. These values must be specified prior to ordering.
SCADA Compatible: Ready for remote monitoring and integration.
Relay Outputs: Equipped with Normally Open (NO) and Normally Closed (NC) relay outputs.
Compliance: Manufactured in accordance with the IEC 61243-5 standard.
Maintenance-Free: Designed for long-term use without maintenance.
Operating Range: Wide operating voltage level from 2kV to 72kV.
Ease of Use: Simple installation with socket-type rear terminals.
Integrated Measurement: Allows for measurement directly through the device front panel.
Overvoltage Protection: Built-in protection against electrical surges.
Customization: Custom production available upon request.